Call us now: 01123860572

INCOL Sumersible Cables

Three Core Flat connecting INCOL Cables are just as important as winding wires are for the submersible pump motor. For trouble free working and satisfaction INCOL cables manufacture 3 core flat cables for use in submersible pump generally confirming to IS: 694/1990, with annealed plain electrolytic grade high conductive copper conductor confirming to IS: 8130/1984 and extruded with specially formulated PVC compound insulation and sheath to withstand and any instantaneous surge voltage and current and impervious to Water, Grease, Oil etc.

CONDUCTOR
Area(Nom) Sqmm
1.50
2.50
4.00
6.00
10.00
16.00
25.00
35.00
50.00
70.00
95.00
Number & Size
of Wire
22/0.30
36/0.30
56/0.30
85/0.30
140/0.30
226/0.30
354/0.30
495/0.30
703/0.30
360/0.50
485/0.50
--
--
--
--
--
126/0.40
196/0.40
276/0.40
396/0.40
360/0.50
485/0.50
INSULATION
Thickness [Nom]mm
0.80
0.80
1.00
1.00
1.00
1.00
1.20
1.20
1.40
1.40
1.60
Core Dia Meter [Nom] mm
3.20
3.85
4.50
5.00
5.90
6.95
8.65
9.90
12.10
13.70
15.80
SHEATH
Overall Dimension
Thickness [Nom]mm
0.80
0.80
1.00
1.00
1.00
1.00
1.20
1.20
1.40
1.40
1.60
Core Dia Meter[Nom] mm
3.20
3.85
4.50
5.00
5.90
6.95
8.65
9.90
12.10
13.70
15.80
Conductor Resistance at 20DegC [Max] Ohms/Km
13.30
7.98
4.50
3.30
1.91
1.21
0.780
0.554
0.386
0.272
0.206
Current Carrying Capacity @ 40 Deg C Amps
14
18
26
31
42
57
72
90
115
143
165


HP Vs Current Approximate full load current for submersible pump motors, 3 phase, 50 Cycle, 415-425 V.
HP
5.0
10.0
12.5
15.0
17.5
20.0
AMP
7.5
14.9
18.9
22.5
25.2
28.4
HP
25.00
35.00
40.00
45.00
50.00
55.00
AMP
35.6
50.00
58.1
62.1
67.50
73.8
 
 
 
 
 
 
 
Maximum Conductor Temperature
Effect of Humidity
Conductor - Elongation At Break
Insulation - Tensile Strength
Sheath - Tensile Strength
Sheath - Elongation At Break
Sheath - Tensile Strength
70 Deg C
NIL
14% Min
125 Kg/cm Min
150% Min
125 Kg/cm Min
150% Min


DERATING FACTORS
Multiply the current carrying capacity of the cable by factors given below for various ambient temperatures.
Ambient Temperature 30 Deg C 35 Deg C 40 Deg C 45 Deg C 50 Deg C
Derating Factor 1.09 1.04 1.00 0.95 0.77